Wall insulation
Exterior wall internal insulation:
According to Clause 6.7.2.2 of Code for fire protection design of building (GB50016-2014): For low occupant density building, Class B1 and above insulation materials with low smoke, low toxicity shall be used. This means Class B1 insulation can be used in internal insulation system for most of residential buildings.
Exterior wall external insulation:
According to item 6.7.5 of Code for fire protection design of building (GB50016-2014),
For residential building:
- Class A insulation shall be used when the height of the building is more than 100m;
- B1 or above shall be used when the height of the building is more than 28m, but no more than 100m;
- B2 or above shall be used when the height of the building is not more than 27m;
This means B2 rigid PU foam can be used in buildings when total height is no more than 27m; B1 rigid PU foam can be used in buildings with total height of not more than 100m.
For public and office building:
- Class A insulation shall be used when the height of the building is more than 50m;
- B1 insulation or above shall be used when the height of the building is more than 24m but not more than 50m;
- B2 or above shall be used when the height of the building is not more than 24m;
This means B2 rigid PU foam can be used in public building and office building when total height is no more than 24m; B1 rigid PU foam can be used in public building and office building when total height is no more than 50m.
For curtain wall building:
- Class A insulation shall be used when the height of the building is more than 24m;
- Class B1 or above shall be used when the height of the building is not more than 24m;
This means B1 rigid PU foam can be used in curtain wall building when total height is no more than 24m.